Products description
KELECTRIC combi drain. GT40 T1 2 12.5kA 3ph.TT/TN-S systems, GT 40 TT/TNS-12.5kA-S, 500101
K'ELECTRIC combined arrester type 1 2 3
Lightning current and surge arresters for TT, TN-S and TN-C networks according to EN/IEC 61643-11, arresters based on varistors and gas discharge arresters, for main power supply systems and busbars with a bar spacing of 40mm, with optical monitoring display, leakage current-free, response time<100ns maximum continuous voltage 300V AC, max. back-up fuse 315A
Lightning impulse current 12.5kA (10/350µs), for buildings with and without external lightning protection, unsecured voltage tap L1 for power supply of APZ field and additional room
Technical data
EAN:4251630408384
Product group: Overvoltage protection
Manufacturer: KELECTRIC
Supplier article number:500101
Width:47mm/3TE
Type:4-pin
This Product was added to our catalogue on 20/11/2019.